Do exit signs need battery backup? In almost every case, yes. To pass inspection and protect occupants, egress legends must remain illuminated for at least 90 minutes when normal power fails. This quick guide explains the national rules (UL 924, NFPA 101, IFC, OSHA), the few valid exceptions, and what inspectors verify—plus links to our pillar resource and related collections.
Last updated: October 2025
Exit signs play a critical role in helping people evacuate safely during emergencies. The common question from owners, electricians, and facility teams—“Do exit signs need battery backup?”—has a simple answer: Yes, in almost every case. National model codes require emergency exit signage to remain illuminated for 90 minutes after a power failure. For a deeper overview of configurations, mounting, arrows, and AHJ planning, see our Exit Signs 101 pillar guide.
Legal & Code Requirements (UL 924, IFC, NFPA 101, OSHA)
Here’s how the primary standards address battery backup and emergency illumination:
- UL 924: Establishes performance requirements for egress lighting equipment. UL 924–listed signs must illuminate within 10 seconds of power loss and stay lit for 90 minutes via internal batteries or a compliant emergency power source. If a sign is not UL 924 listed, it likely isn’t code compliant.
- NFPA 101 (Life Safety Code): Requires illuminated signs along the egress path and mandates 90-minute emergency illumination. Transfer to emergency power must occur automatically.
- IFC (International Fire Code): Aligns with UL/NFPA, requiring exit signage to be continuously visible and to remain illuminated for 1.5 hours without normal power.
- OSHA: 29 CFR 1910.37 requires exits to remain visible and illuminated during outages. While OSHA doesn’t name batteries specifically, it requires the performance (90-minute illumination)—internal battery packs are the most common way to achieve this.
Pro Tip: Look for the UL 924 label—it’s the fastest way to confirm compliance.
Need product options? Start at Exit Signs, or consider Self-Testing models to automate monthly/annual checks.
Where Battery Backup Is Not Required
Although internal battery backup is the norm, there are legitimate alternatives—each still must meet the same 90-minute performance and be properly listed:
- Self-Luminous Signs (Tritium): Tritium tubes glow continuously with no electricity or batteries. See Tritium Exit Signs.
- Photoluminescent Signs: “Glow-in-the-dark” signs charge under ambient light and glow during outages—no batteries or wiring. Explore Photoluminescent options.
- Central Emergency Power: If a sign is fed by a generator or inverter that reliably provides 90 minutes of backup, an internal battery is not required.
Note: These paths must still satisfy visibility, duration, and listing requirements. Always confirm with your AHJ before selecting a non-battery approach.
What Building Inspectors Look For
Expect your AHJ to verify both the listing and the emergency performance. Common checkpoints include:
- Function Test: Will the sign illuminate without building power?
- Listing & Markings: Is the fixture clearly labeled as UL 924 listed?
- Visibility & Condition: Is the legend unobstructed, legible, and the housing intact?
- Battery/Status: For battery units, is the charge/status indicator normal (or the self-test indicator green)?
- Duration Proof: Some inspectors ask for evidence of a successful 90-minute test.
Alert: Exit signage failures are a frequent inspection issue. Review the AHJ checklist in our pillar to avoid common mistakes.
Best Practices for Compliance & Maintenance
- Monthly: Press the test button (or confirm auto-test) for ~30 seconds on battery power; log the result.
- Annually: Run a 90-minute discharge; document pass/fail and any corrective actions.
- Keep a Log: Maintain simple records (location, date, pass/fail, notes) for audits and AHJ visits.
- Battery Lifecycle: Replace packs every 3–5 years, or sooner if a unit fails its test.
- Consider Self-Testing: Auto-diagnostic units reduce labor and surface faults proactively—browse Self-Testing Exit Signs.
Tip: Keep spare batteries and a printed test log in the maintenance room to speed inspections.
Final Thoughts
Battery-backed egress legends are a life-safety essential—and a code requirement in nearly all scenarios. Whether you’re retrofitting or building new, verify your devices are UL 924–listed and capable of 90-minute operation. If you’re not using a listed emergency model (or an approved alternative like photoluminescent, tritium, or central power), you’re likely out of compliance.
Next step: Start with Exit Signs, or learn how auto-test reduces maintenance in our self-testing benefits guide. For a full code overview, see the UL 924 Compliance Guide.