Flush-Recessed LED Emergency Light – 350 lm, Adjustable Optics

SKU: FRM-BL
Regular price $157.68

Got questions?

Give us a call 800-847-1955!

Flush-Recessed LED Emergency Light – 350 lm, Adjustable Optics

The FRM Series Flush-Recessed LED Emergency Light stays hidden until needed—only a slim trim plate is visible during normal operation. In an outage, two adjustable LED optics tilt out automatically to deliver bright, uniform egress lighting with up to 55 ft spacing. Each unit ships with rectangular and oval trim plates, bar hangers for drywall or T-bar ceilings, and IC-rated back-box construction for code-compliant installs. Explore more LED recessed emergency lighting .

Specs, documents, buying checks, accessories, and FAQs are organized below from product fields for easier review.

Buying support

Product details and buying checks

Review specs, documents, buying checks, compatible products, and FAQs before ordering.

  • UL 924
  • Damp Location
  • 120/277 VAC
  • 90 min Runtime
  • Pop-Out Optics
  • Up to 55 ft Spacing
  • Self-Testing (opt.)
  • NYC Code
  • CEC Title 20
  • NFPA 101

Key features

  • Architectural flush, recessed ceiling mount with IC-rated back-box.
  • Two low-profile LED optical assemblies ( 2 × 1 W each; 4 W total ) that tilt out on power loss.
  • Spacing at 10 ft MH: up to 55 ft (3 ft path) and up to 49 ft (6 ft path), aim-dependent (0–15° in 1.7° clicks).
  • Dual-primary 120/277 VAC , 60 Hz; maintenance-free 4.8 V Ni-Cd battery.
  • 90 minute emergency runtime; 24-hour recharge; solid-state transfer; LVD & brownout protection; test button with bi-color status LED.
  • Injection-molded UL 94 5VA thermoplastic trim plates (rectangular & oval) over a steel housing.
  • Operating temperature: 10–50 °C (50–122 °F); Damp Location listed.
  • Finishes: White or Black ; NYC Emergency Code compliant; CEC Title 20.
Product family Emergency Lights
SKU FRM-BL
Listing UL 924
Runtime/service 90 minute emergency runtime; 24-hour recharge; solid-state transfer; LVD & brownout protection; test button with bi-color status LED
Environment Damp Location listed
Power LED optical assemblies ( 2 × 1 W each; 4 W total ) that tilt out on power loss

Documents

Related NYC Emergency Light Guides

NYC Emergency Lighting Requirements Recessed NYC Exit Signs & Emergency Lights

Spec Sheet

Download FRM Recessed Emergency Light Spec Sheet (PDF)

Illumination
  • Each optical assembly: 2 × 1 W long-life LEDs ( 4 W total ), ~ 88 lm/W efficacy.
  • Click-in aiming: 0–15° vertical in 1.7° increments for precise coverage.
  • Sample spacing at 10 ft MH: 3 ft path up to 55 ft ; 6 ft path up to 49 ft (aim-dependent).
Electrical
  • Universal 120–277 VAC , 60 Hz input.
  • Maintenance-free 4.8 V Ni-Cd battery; 90 min emergency run time; 24 hr max recharge.
  • Solid-state transfer, low-voltage disconnect , brownout protection.
  • Bi-color status LED: green = normal, red = check battery.
Housing / Finish
  • Steel recessed housing with UL 94 5VA flame-retardant thermoplastic trim plates.
  • Back-box depth: 2.75" • Overall depth: 2.875" .
  • White or Black trim (both paintable); rectangular & oval plates included.
Mounting
  • Ceiling mount only (recessed); adjustable bar hangers extend to 24" for T-bar or joists.
  • Conduit entry top/side; pre-stripped AC leads for quick wiring.
Options
  • G2 — Guardian self-test / self-diagnostics (monthly / 6-mo / annual).
  • WG-S — Wire guard (back mount) • XG-1 — Polycarbonate guard (back mount).
Warranty / Listings
  • 5-year warranty on electronics & housing; 5-year prorated on Ni-Cd battery.
  • UL 924 Listed for Damp Locations ; meets or exceeds NFPA 101 , NEC , OSHA ; CEC Title 20 ; NYC code requirements.
Compliance notes
  • Confirm final fixture placement, runtime, and local AHJ acceptance for the project.