Fluorescent Emergency Ballast – 120/277V, T5/T8/T12 Compatible, 1400 Lumens | UL 924
Couldn't load pickup availability
Fluorescent Emergency Ballast – 1400 Lumen Output, 120/277V, UL 924 Listed
This fluorescent emergency ballast allows a fixture to operate in both normal and emergency modes. During power failure, it switches to battery operation and powers one or two lamps for 90 minutes at up to 1400 lumens. Compatible with many T5, T8, and T12 fluorescent lamps, it features a compact steel case, high-temperature NiCad battery, test switch, and indicator light. Suitable for factory or retrofit installation.
Download Fluorescent Emergency Ballast Spec Sheet (PDF)
Lamp Compatibility Chart
Lamp Type | Wattage (W) | Initial Lumens (1 Lamp) | Initial Lumens (2 Lamps) |
---|---|---|---|
T5 | 14 | 900 | 950 |
T5 | 21 | 1050 | 1100 |
T5 | 28 | 1150 | 1225 |
T5 | 35 | 1200 | — |
T5HO | 24 | 1100 | 1200 |
T5HO | 54 | 1350 | 1400 |
T5HO | 39 | 1200 | 1300 |
T8 | 17 | 1000 | 1100 |
T8 | 25 | 1100 | 1200 |
T8 | 28 | 1150 | 1250 |
T8 | 32 | 1300 | 1350 |
T8 | 40 | 1350 | 1400 |
T8HO | 44 | 1350 | — |
T8 | 51 | 1400 | — |
T8 | 59 | 1400 | — |
T8HO | 86 | 1400 | — |
T12 | 20 | 700 | 800 |
T12 | 25 | 750 | 800 |
T12 | 30 | 800 | — |
T12 | 34 | 850 | 975 |
T12 | 40 | 950 | 1050 |
T12 | 75 | 1300 | — |
T12HO | 95 | 1400 | — |
T12HO | 110 | 1400 | — |
T12HO | 160 | 1400 | — |
T12HO | 215 | 1400 | — |
Note: In 2-lamp operation, lumens are split equally between the two lamps. For LED retrofit compatibility, contact the lamp manufacturer.
Features & Benefits
- UL 924 Listed for factory or field installation
- Operates one or two lamps for 90 minutes in emergency mode
- Delivers 700–1400 lumens total depending on lamp configuration
- Compatible with T5, T8, T12 fluorescent lamps (see chart)
- High-temperature, maintenance-free NiCad battery
- Includes test switch and charge indicator light
Electrical Specifications
- Input Voltage: 120/277V, 60Hz
- Input Power: 3.3 watts
- Battery: NiCad, sealed, maintenance-free
- Operating Temperature: 0°C to 50°C (32°F to 122°F)
Installation
- Mounts in wireway or on top of fluorescent fixture
- Remote mounting up to 50 feet (max)
- Suitable for indoor use (not for heated air or hazardous fixtures)
Housing / Dimensions
- Durable painted steel housing
- Length: 13.3”, Width: 2.4”, Height: 1.5”
- Mounting Center: 12.8”
Compliance & Warranty
- Meets UL 924, NEC, and NFPA 101 requirements
- 5-year limited warranty
Frequently Asked Questions
Which lamps are compatible?
Compatible with T5, T5HO, T8, T12, and T12HO fluorescent lamps up to 215W. See the lamp compatibility chart for lumen output per type.
Can I power two lamps?
Yes. In two-lamp mode, lumen output is split evenly between both lamps (e.g., 1400 lm = 700 lm per lamp).
Is this suitable for LED tubes?
Some LED retrofit tubes are compatible. Contact the LED lamp manufacturer for confirmation.
What’s the maximum distance for remote mounting?
Up to 50 feet from the lamp, or half the lamp-to-ballast distance allowed by the AC ballast.
Does it include a test switch?
Yes. A test switch and charge indicator LED are included with the accessory kit.